防火卷帘门维护保养的小妙招

来源:http://www.jnyuqilin.com/  发布时间:2022-02-16 19:59:07

我们都知道防火卷帘门会起到防火的作用,大家对其了解多少?知道该门的维护保养技巧有哪些吗?是不是不清楚?接下来,山东防火卷帘门厂家将在下文为大家简单的介绍一下,希望能帮到大家。
We all know that the fireproof rolling shutter door will play the role of fire prevention. How much do you know about it? Do you know the maintenance skills of the door? Is it not clear? Next, Shandong fireproof rolling shutter door manufacturer will give you a brief introduction below, hoping to help you.
防火卷帘门处在联动状态下降到底后,按动卷帘门两侧的任意一个手动钮,门应能够上升到达限位后(或者经延时)重新下降到底。这也是对该卷帘门的基本要求。卷帘门两侧的手动按钮的升、降、停试验,应能按照指令运行,运行应平稳,无阻滞,更不能出现帘板运行速度不均匀、帘板堆积甚出轨现象。
After the fire-proof rolling shutter door is in the linkage state and drops to the bottom, press any manual button on both sides of the rolling shutter door, and the door shall be able to rise to the limit (or drop to the bottom after delay). This is also the basic requirement for the rolling shutter door. The lifting, lowering and stopping tests of the manual buttons on both sides of the rolling shutter door shall be able to operate in accordance with the instructions, and the operation shall be stable without blocking, and the phenomenon of uneven running speed of the shutter plate, accumulation of the shutter plate and even derailment shall not occur.
模拟火灾信号进行联动试验,要求防火卷帘门应能按照正常程序下降,消防控制室显示的内容、部位应与实际一致。手动应急装置的试验。使用手动拉链提升防火卷帘门,使用手动速放装置下放防火卷帘门,防火卷帘门应能顺利运行。检查防火卷帘门的封堵是否完好,有无破坏现象。以上检查应认真做好记录,对发现的问题应及时,以免影响使用。
Conduct linkage test by simulating the fire signal. It is required that the fire rolling shutter door can be lowered according to the normal procedure, and the contents and positions displayed in the fire control room shall be consistent with the actual situation. Test of manual emergency device. The manual zipper is used to lift the fireproof rolling shutter door, and the manual quick release device is used to lower the fireproof rolling shutter door. The fireproof rolling shutter door shall be able to operate smoothly. Check whether the sealing of the fireproof rolling shutter door is intact and damaged. The above inspections shall be carefully recorded, and the problems found shall be solved in time to avoid affecting the use.